Siemens SIMATIC Compact FF Link - Connecting; Electrical Isolation and Grounding

Siemens SIMATIC Compact FF Link
102 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting
6
6.1 Electrical isolation and grounding
Introduction
You can wire the 24 V power supply to the described modules depending on the requirements
of your system configuration:
Grounded configuration
Ungrounded configuration
Power supply
The 24 V DC power supply is connected by a 2-pin connector from the bottom. You can find
additional information on this in section "Connecting the power supply (Page 37)".
Electrical isolation for Compact FF Link
The following areas of the Compact FF Link are electrically isolated from one other:
24 V power supply
PROFIBUS DP
FOUNDATION Fieldbus
Reference
You can find more detailed information about these topics in Operating Instructions
DP/PA
coupler, Active Field Distributor, DP/PA Link and Y Link
:
General rules and regulations
Grounding the active field distributors
Operation with grounded supply
Operation with ungrounded reference potential
Due to the same physical conditions, the specifications made there apply accordingly.
For information on the cable used, refer to section Article numbers (Page 89).
Compact FF Link
Operating Instructions, 03/2015, A5E35651552-AA 33