Description of the components
3
3.1 Compact FF Link
Functions
Interface module (DPV1 slave) on the higher-level DP master system (in HW Config:
IM 655‑5 FF)
Field device coupler for a lower-level FF bus system (in HW Config: Field Device Coupler)
FF Link master functionality
Link Active Scheduler (LAS) for the central communication control of the distributed
communication of the FF segment.
Properties
Conversion of physical transmission characteristics to symmetrical physical bus
characteristics according to IEC 61784‑1 CP 1/1
Integrated power supply for FF (Power Conditioner)
Connection of up to 31 FF devices, max. current consumption of all components 500 mA
Automatic bus termination enables easy commissioning
Transmission rates:
On the DP master system: 9.6 kbps to 12 Mbps
On the FF segment: 31.25 kbps
Support of system modifications during operation
In non-redundant mode
In redundancy mode
Diagnostics via LEDs and the user program
Extended environmental conditions