Parameter
4.3 Configuration control (option handling)
IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
26 Manual, 10/2018, A5E32840985-AB
Control data record
A control data record 196 is defined for the configuration control that receives a slot
assignment.
Table 4- 3 Control data record
Byte
Element
Code
Explanation
0
Block length
4 + number of slots
Header
1 Block ID 196
2
Version
3
3
Version
0
4 Assignment of config-
ured slot 0
Real slot 0 Control element
Describes in each
element which real
slot in the device is
assigned to the con-
figured slot.
5 Assignment of config-
ured slot 2
Real slot 2
:
:
:
4 + (max. slot - 1) Assignment of config-
ured maximum slot
Real maximum slot
Control element
Each element must include the following information about the slot:
Assignment of configured slot real slot
Table 4- 4 Code of control element
Byte
Bit
Meaning
Assignment of configured slot
(e.g. in byte 5)
0 to 7 01111111: Module not available
00000000 up to maximum slot: Real slot