Interrupts and diagnostic, error, and system alarms
5.3 Alarms
IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
Manual, 10/2018, A5E32840985-AB
47
USI structure = W#16#0007
Table 5- 14 USI structure = W#16#0007
W#16#0007 Manufacturer-specific diagnostics if
the configuration of the interface
module power supply is different from
the parameterized configuration
Followed by 3 reserved bytes
Error IM power supply: Power supply <bit 0 in the least significant byte can be 0 or 1>
Power supply of the interface
module
B#16#00 Power supply of the interface module
1
B#16#01 Power supply of the interface module
Invalid configuration states of the ET 200MP on PROFINET IO
Invalid configuration states
The following invalid configuration states of the ET 200MP lead to a short failure of the
ET 200MP IO device or prevent the exchange of user data with the I/O modules.
● More than two power supply modules (PS) inserted to the right of the interface module
● Number of modules exceeds maximum configuration
● Faulty backplane bus (e.g., additional IM present).
● I/O modules of a power segment consume more power than can be provided (overload).
In the case of an overload, the interface module provides diagnostic information,
cyclically checks the connection to the backplane bus and re-establishes it as soon as
possible.
You can find additional information on maximum configuration, power budget and power
segments in the system manual S7-1500, ET 200MP Automation system
(https://support.industry.siemens.com/cs/ww/en/view/59191792).
Status and error displays (Page 36)