Response times
B
B.1
Response times of the ET 200MP
Introduction
The response time of the IM 155-5 PN HF is made up of:
The update time configured for the IM as IO device.
plus
The backplane bus cycle time.
Note
Validity of the formula
The following formula does not apply to Shared Device mode.
Backplane bus cycle time
The backplane bus cycle time is the time the interface module requires to output new output
data, read new input data and then copy them to the PROFINET send buffer.
The backplane bus cycle time in μs is made up as follows:
(Number of output data in bytes + number of output addresses) x 0.0668 + 1.6131
(rounded up)
plus
(Number of input data in bytes + number of input addresses) x 0.0959 + 2.5901
(rounded up)
plus
Operating system processing time (500 μs).