Loading...
Parameter
4.3 Configuration control (option handling)
IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
Manual, 10/2018, A5E32840985-AB
33
Data record of the example
The following table shows the structure of the control data record for the above example.
Table 4- 9 Data record for example "Extending the configuration"
Byte
Element
Code
Explanation
0
Block length
17
Header
1 Block ID 196
2
Version
3
3
Version
0
4
Slot 0
00000000
B
The configured slot 0 is the real slot 0.
5
Slot 2
00000010
B
The configured slot 2 is the real slot 2.
6
Slot 3
00000011
B
The configured slot 3 is the real slot 3.
7
Slot 4
00000100
B
The configured slot 4 is the real slot 4.
8
Slot 5
00000101
B
The configured slot 5 is the real slot 5.
9
Slot 6
00001011
B
The configured slot 6 is the real slot 11.
10
Slot 7
00001100
B
The configured slot 7 is the real slot 12.
11
Slot 8
00001101
B
The configured slot 8 is the real slot 13.
12
Slot 9
00001001
B
The configured slot 9 is the real slot 9.
13
Slot 10
00001010
B
The configured slot 10 is the real slot 10.
14
Slot 11
00000110
B
The configured slot 11 is the real slot 6.
15
Slot 12
00000111
B
The configured slot 12 is the real slot 7.
16
Slot 13
00001000
B
The configured slot 13 is the real slot 8.