Parameter
4.3 Configuration control (option handling)
IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
Manual, 10/2018, A5E32840985-AB
35
Data record of the example
The following table shows the structure of the control data record for the above example.
Table 4- 10 Data record for example "Combining configurations"
Byte
Element
Code configura-
tion 1
Code configura-
tion 2
Explanation
0
Block length
17
Header
1 Block ID 196
2
Version
3
3
Version
0
4
Slot 0
00000000
B
00000000
B
The configured slot 0 is the real slot 0.
5
Slot 2
00000010
B
00000010
B
The configured slot 2 is the real slot 2.
6
Slot 3
00000011
B
00000011
B
The configured slot 3 is the real slot 3.
7
Slot 4
00000100
B
00000100
B
The configured slot 4 is the real slot 4.
8
Slot 5
00000101
B
00000101
B
The configured slot 5 is the real slot 5.
9 Slot 6 01111111
B
00000110
B
The configured slot 6 does not exist (configuration 1).
The configured slot 6 is the real slot 6 (configuration 2).
10 Slot 7 01111111
B
00000111
B
The configured slot 7 does not exist (configuration 1).
The configured slot 7 is the real slot 7 (configuration 2).
11 Slot 8 00000110
B
00001000
B
The configured slot 8 is the real slot 6 (configuration 1).
The configured slot 8 is the real slot 8 (configuration 2).
12 Slot 9 00000111
B
00001001
B
The configured slot 9 is the real slot 7 (configuration 1).
The configured slot 9 is the real slot 9 (configuration 2).
13 Slot 10 00001000
B
00001010
B
The configured slot 10 is the real slot 8 (configuration 1).
The configured slot 10 is the real slot 10 (configuration 2).
14 Slot 11 01111111
B
00001100
B
The configured slot 11 does not exist (configuration 1).
The configured slot 11 is the real slot 12 (configuration 2).
15 Slot 12 01111111
B
00001101
B
The configured slot 12 does not exist (configuration 1).
The configured slot 12 is the real slot 13 (configuration 2).
16 Slot 13 00001001
B
00001011
B
The configured slot 13 is the real slot 9 (configuration 1).
The configured slot 13 is the real slot 11 (configuration 2).