5.1 Connecting measuring sensors
2AI U HF analog electronic module (6ES7134-4LB02-0AB0)
Manual, 04/2007, A5E01076007-01
23
Non-isolated measuring encoders
The non-isolated measuring encoders are connected to the local ground potential. You must
connect M
ANA
to the ground potential. Depending on local conditions or interference,
potential differences U
CM
(static or dynamic) can occur between the locally distributed
measuring points.
If the permitted value for U
CM
is exceeded, there must be equipotential bonding conductors
between the measuring points.
The following schematic representation illustrates the connection of non-isolated measuring
encoders to an optically isolated analog input module.