Digital Electronics Module 1 F-RO DC24V/5A AC24..230V/5A
2.3 Terminal Assignment for EM 1F-RO DC24V/5A AC24..230V/5A
Product Information for the Distributed I/O System ET 200S, Fail-Safe Systems Manual
Product information, 07/2006, A5E00825271-01
2-5
Table 2-3 Terminal assignment of TM-P30S44-A0 and TM-P30C44-A0
Terminal Designation
3 IN P Terminal for control voltage DC 24V
4 IN M Terminal for control voltage ground
A4 AUX 1 at TM-E...46-A1: AUX 1 bus implemented. Connection with the
terminals A3 to A16 for any PE contact.
Individual grouping of load current supply is possible.
A3 AUX 1 at TM-E...46-A1: AUX 1 bus implemented. Connection with the
terminals A3 to A16 for any PE contact.
Individual grouping of load current supply is possible.
7 IN P Terminal for control voltage DC 24V
8 IN M Terminal for control voltage ground
A8 AUX 1 at TM-E...46-A1: AUX 1 bus implemented. Connection with the
terminals A3 to A16 for any PE contact.
Individual grouping of load current supply is possible.
A7 AUX 1 at TM-E...46-A1: AUX 1 bus implemented. Connection with the
terminals A3 to A16 for any PE contact.
Individual grouping of load current supply is possible.
9 OUT 1 (13)
10 OUT 1 (14)
13, 14: Contacting element, channel 0 for fail-safe switching load 1
11 OUT 2 (23)
12 OUT 2 (24)
23, 24: Contacting element, channel 1 for fail-safe switching load 2
A12 AUX 1 at TM-E...46-A1: AUX 1 bus implemented. Connection with the
terminals A3 to A16 for any PE contact.
Individual grouping of load current supply is possible.
A11 AUX 1 at TM-E...46-A1: AUX 1 bus implemented. Connection with the
terminals A3 to A16 for any PE contact.
Individual grouping of load current supply is possible.
13 OUT 1 (13)
14 OUT 1 (14)
13, 14: Contacting element, channel 0 for fail-safe switching load 1
15 OUT 2 (23)
16 OUT 2 (24)
23, 24: Contacting element, channel 1 for fail-safe switching load 2
A16 AUX 1 at TM-E...46-A1: AUX 1 bus implemented. Connection with the
terminals A3 to A16 for any PE contact.
Individual grouping of load current supply is possible.
A15 AUX 1 at TM-E...46-A1: AUX 1 bus implemented. Connection with the
terminals A3 to A16 for any PE contact.
Individual grouping of load current supply is possible.
Caution
Parallel wiring must be carried out if high current is likely to occur on OUT 1 or OUT 2.
• for OUT 1: the terminals 9/10 and 13/14
• for OUT 2: the terminals 11/12 and 15/16
Otherwise, an overheating of the terminal caused by the current load cannot be ruled out.