2.5 2.5 Diagnosis of the EM 1 F-RO DC24V/5A AC24..230V/5A
Output status display
The output status display on the F-RO-module has the following behavior:
• Relay not activated: LED does not light up
• Relay is activated: LED lights up
• Relay not activated and relay contact welded: LED lights up
Causes of Errors and Corrective Measures
For diagnostic purposes you can evaluate the F-Systems S7 Distributed Safety output
"DIAG" des FB 216 "F_FDBACK," if you use this application block in your safety program for
the readback of relay contacts (refer to the manual
S7 Distributed Safety, Configuration and
Programming
).
2.6 2.6 Technical Data of the EM 1 F-RO DC24V/5A AC24..230V/5A
Overview
Technical Specifications
Dimensions and Weight
Dimensions W x H x D (mm) 30 x 81 x 52
Weight Approx. 90 g
Module Specific Data
Number of outputs
• Relay outputs
1 (2 channels)
Assigned address area
• In the I/O area for inputs
2 bits
• In the I/O area for outputs
--
Length of cable
• unshielded for load contact
max. 200 m
• shielded for load contact
max. 200 m
• control cable (input)
max. 10 m
Maximum safety class attainable
• according to IEC 61508
SIL3
• according to EN 954
Cat. 4
Safety parameters SIL3
Low demand mode (average probability of failure
on demand)
< 1.00E-05
High demand/continuous mode (probability of a
dangerous failure per hour)
< 1.00E-09