Digital Electronics Module 1 F-RO DC24V/5A AC24..230V/5A
2.6 Technical Data of the EM 1 F-RO DC24V/5A AC24..230V/5A
Product Information for the Distributed I/O System ET 200S, Fail-Safe Systems Manual
Product information, 07/2006, A5E00825271-01
2-11
Technical Specifications
Current consumption
From backplane bus
max. 10 mA
From control voltage (IN P, IN M)
max. 100 mA
Power dissipation of the module avg. 2.1 W
Status, Interrupts, Diagnostics
Status display green LED
Diagnostic Functions
Diagnostic information can be displayed
no
Data for Selecting an Actuator*
Output current
Thermal constant current
max. 5 A
Minimum load current
5 mA
Contact wiring (internal) no
On the relay outputs
no
Wire break monitoring no
Parallel connection of 2 outputs possible, no increase in load current
Digital input control possible
Switching frequency
With resistive load
max. 2 Hz
With inductive load according to IEC 947-5-1,
DC13
max. 0.1 Hz
With inductive load according to IEC 947-5-1,
AC15
max. 2 Hz
Limitation (internal) of the voltage induced on the
circuit interruption
no
Short-circuit protection of output no, external fusible cutout 6 A operating class
gL/gG
Time, Frequency
Switching time avg. 13 ms
Release time avg. 16 ms
Protection against Overvoltage
Protection of outputs from surge load in
accordance with IEC 61000-4-5 (no protection
elements required)
Symmetrical
Channel 1 (9/13) against (10/14)
Channel 2 (11/15) against (12/16)
+1 kV; 1.2/50 μs
Unsymmetrical
Channel 1 (9/13) or (10/14) against PE
Channel 2 (11/15) or (12/16) against PE
+2 kV; 1.2/50 μs
*: For more information on the requirements for sensors and actuators see