Ex-DI 4xNAMUR
Ex-DI 4xNAMUR
A5E50377423-AB, 03/2023
13
You must observe the guidelines according to DIN EN IEC 60079-17 for functional
checks.
Derating
The table shows the maximum permissible output current for the Ex-Power Module
depending on the installation position and the ambient temperature.
Mounting position
Ambient temperature
Output current
Horizontal installation
From -40 °C to 60 °C
0.8 A
From -40 °C to 70 °C
0.6 A
Vertical installation
From -40 °C to 50 °C
0.8 A
From -40 °C to 60 °C
0.6 A
Specific conditions of use
CAUTION
Specific conditions of use
1. This equipment shall be installed in an enclosure with an ingress protection of at
least IP54 in accordance with EN 60079-0 and EN 60529. The installation shall also
ensure Pollution Degree 2 (as defined in EN 60664-1) inside the enclosure. All
circuits shall be limited to Overvoltage category I or II. These requirements apply
even when installed in a non-hazardous area.
2. The earth connection of the mounting rail shall be connected to the local potential
equalization system per applicable installation standard.
3. Transient protection shall be provided that is set at a level not exceeding 140 % of
the peak rated voltage value at all supply terminals to the equipment, or at most
set at 119 V.
Maintenance
The Ex-I/O modules are maintenance-free.
In general, pulling or plugging modules is not allowed in Zone 2. Before starting work,
make sure that there is no explosive atmosphere or that the power supply is switched
off.
For repairs, you must send the I/O module to the manufacturing location. The repair
may only be carried out there.

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals