EasyManua.ls Logo

Siemens SIMATIC HMI TP27 - Page 143

Siemens SIMATIC HMI TP27
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13-2
TP27, TP37 Equipment Manual
Release 01/00
Before commissioning the Touch Panel please observe the following:
!
Caution
S With the SIMATIC S5, compression of the internal program memory on
the PLC (PU “Compress” function, integrated FB COMPR) is not allowed
when a Touch Panel is connected. Compression modifies the absolute ad-
dresses of the blocks in the program memory. As the Touch Panel reads the
address list only during startup, it does not detect any address modifica-
tions and accesses the wrong memory areas.
If compression is inevitable during routine operation, switch off the Touch
Panel prior to compression.
S In hazardous areas, always de–energize the Touch Panel before unplugging
connectors.
Do not touch the screen of the Touch Panel until after the initialization phase
when the menu illustrated in figure13-2 or figure 13-3 appears.
The signal tone is not active during startup.
Before
commissioning
Note regarding TP
start–up
Commissioning

Table of Contents

Related product manuals