C-5
TP27, TP37 Equipment Manual
Release 01/00
Remedy:CauseMessage
259 Transfer of a data record to the PLC is taking too long.
Example:
PLC is not acknowledging data record or very large data
records are being transferred.
Check PLC program. In the case of large
data records no modifications are necessary
as the function is being processed correctly.
260 Operating mode of PLC does not match the configura-
tion.
Change operating mode of PLC.
261 The data in this data record is no longer consistent and it
can therefore no longer be used.
Edit data record and check that all entries
are correct.
262 Password or query window already in use by another
function.
Complete first function then execute de-
sired function again.
263 Specified remaining buffer space for messages has been
reached!
Configure smaller remaining buffer, delete
event/alarm message buffers.
264 Message buffer overflow. The overflow messages are printed out if
so specified in the configuration.
265 The number of passwords issued has already reached 50.
You can not enter any more passwords.
If you wish to issue additional passwords,
you must first delete some of the existing
ones.
266 The field configured in the PLC job does not exist. Change the parameters of the PLC job and
retransfer the configuration.
303 Fault in connection with PLC.
S5: this error may occur when transferring large data
records. In such cases the watchdog is activated.
Check PLC status.
S5: set value in data word 98 to at least
2000.
305 Data block number missing. Set up data block or change configuration.
306 Incorrect CPU specified under ”PLC –> Parameters”. Change configuration and retransfer.
307 ...
311
Variable not present on PLC Check configuration of process link.
316 Active password level insufficient for menu item Enter password with higher password level.
339 Startup completed. Communication with PLC has been re-
sumed.
340 Status processing in progress on PU/PC. The OP can not
be used while this is going on.
341 Internal error
With non-Siemens connections: data block error
342 Network node has illegal address. Max. addresses:
S7-MPI: 32
PROFIBUS-DP: 128
343 You are attempting to edit a variable of a type that can
not be edited in a recipe: currently applies to ARRAY
variables only.
350 PLC is performing initialization. You can not enter any
setpoints during initialization. Scrolling of screens is
possible.
This operating mode may be set by the
PLC programmer.
351 PLC has completed initialization. You can resume enter-
ing setpoints once this message has appeared.
S
y
stem Messa
g
es

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC HMI TP27 and is the answer not in the manual?

Siemens SIMATIC HMI TP27 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC HMI TP27
CategoryTouch Panel
LanguageEnglish

Related product manuals