IM151-1 HIGH FEATURE interface module (6ES7151-1BA02-0AB0)
Manual, 03/2008, A5E01075975-02
7
Properties
1
1.1 IM151-1 HIGH FEATURE interface module (6ES7151-1BA02-0AB0)
Properties
The IM151-1 HIGH FEATURE interface module has the following features:
It connects the ET 200S with PROFIBUS DP via the RS 485 interface.
There is no restriction on the SIMATIC S7 for the maximum parameter length. It is
normally 244 bits.
The maximum address space is 244 bytes for inputs and 244 bytes for outputs.
Operation as a DPV0 or DPV1 slave
A maximum of 63 modules can be operated with the IM151-1 HIGH FEATURE.
The maximum bus length at the backplane bus is 2 m.
Supports option handling and the status byte for power modules.
synchronizable with the DP cycle (cycle synchronization).
The firmware can be updated via PROFIBUS DP using HW CONFIG.
Safety-related I-slave-slave-communication via PROFIBUS DP. You can find the
description of this function in the
S7 Distributed Safety Configuration and Programming
manual.
Identification data
Direct data exchange
Operation as DPV1 slave on the Y switching
Use of fail-safe modules