Configuration and operation
4.5 Telecontrol communication (CP 1542SP-1 IRC)
CP 1542SP-1, CP 1542SP-1 IRC, CP 1543SP-1
54 Operating Instructions, 01/2017, C79000-G8976-C426-03
Connection establishment
Specifies the communications partner that establishes the connection (always the CP).
Partner port
Port number of the communications partner
"Connection to redundant partner" (only with DNP3 / IEC)
Redundancy mode
Enable the option if the communications partner is a redundant master.
For information on the other parameters see above.
"Advanced settings"
Partner monitoring time (only with DNP3 / IEC)
If the CP does not receive a sign of life from the communications partner within the
configured time, the CP interprets this as a fault/error on the partner. If you enter 0, the
function is deactivated.
Report partner status (connection to partner)
If the function is enabled, the CP signals the status of the connection to the
communications partner to the CPU.
Bit 0 of "PLC tag for partner status" (data type WORD) is set to 1 if the partner can be
reached.
Bit 1 is set to 1 if all the paths to the remote partner are OK (useful with redundant
paths).
Bits 2-3 indicate the status of the send buffer (frame memory).
The following values are possible:
- 0: Send buffer OK
- 1: Send buffer threatening to overflow (more than 80 % full).
- 3: Send buffer has overflowed (fill level 100 % reached).
As soon as the fill level drops below 50%, bits 2 and 3 are reset to 0.
Bits 4 to 15 of the PLC tags are not used and do not need to be evaluated in the program.
DNP3-specific settings
DNP3 level
DNP3 conformity level supported by the partner.
Event transmission mode
Mode with which the frames in the send buffer of the CP (events) are transferred:
Chronological transfer of individual frames
or
Block-by-block transfer of the frames of a data point

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET ET 200SP and is the answer not in the manual?

Siemens SIMATIC NET ET 200SP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET ET 200SP
CategoryNetwork Router
LanguageEnglish

Related product manuals