Article number 6ES7515-2RN03-0AB0
–
Updating times The minimum value of the update time also
depends on communication share set for
PROFINET IO, on the number of IO devices, and
on the quantity of configured user data
Update time for RT
–
for send cycle of 1 ms 1 ms to 512 ms
2. Interface
Interface types
•
RJ 45 (Ethernet) Yes; X2
•
Number of ports 1
•
integrated switch No
Protocols
•
IP protocol Yes; IPv4
•
PROFINET IO Controller No
•
PROFINET IO Device No
•
SIMATIC communication Yes; Only Server
•
Open IE communication Yes
•
Web server No
•
Media redundancy No
Interface types
RJ 45 (Ethernet)
•
100 Mbps Yes
•
Autonegotiation Yes
•
Autocrossing Yes
•
Industrial Ethernet status LED Yes
Protocols
PROFIsafe No
Number of connections
•
Number of connections, max. 128
•
Number of connections reserved for
ES/HMI/web
10
•
Number of S7 routing paths 16
Redundancy mode
•
PROFINET system redundancy (S2) Yes
•
PROFINET system redundancy (R1) No
Media redundancy
–
MRP Yes; MRP Automanager according to IEC 62439-2
Edition 2.0
–
MRP interconnection, supported Yes; as MRP ring node according to IEC 62439-2
Edition 3.0
–
MRPD No
39
Technical specifications
CPU 1515R-2 PN (6ES7515-2RN03-0AB0)
Equipment Manual, 11/2022, A5E42009914-AD