Technical data of CPU 31x
7.5 CPU 315-2 PN/DP
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
7-21
Technical data
Assembly
Racks Max. 4
Modules per rack 8
Number of DP masters
Integrated
1
via CP
2
Number of function modules and communication processors you can operate
FM
Max. 8
CP (PtP)
Max. 8
CP (LAN)
Max. 10
Time-of-day
Real-time clock Yes (hardware clock)
Factory setting
DT#1994-01-01-00:00:00
Buffered
Yes
Buffered period
Typically 6 weeks (at an ambient temperature of
104 °F)
Behavior of the clock on expiration of the
buffered period
The clock keeps running, continuing at the time-
of-day it had when power was switched off.
Behavior of the realtime clock after POWER
ON
The clock continues running after POWER OFF.
Accuracy
Deviation per day: < 10 s
Operating hours counter 1
Number
0
Value range
2
31
hours
(if SFC 101 is used)
Granularity
1 hour
Retentive
yes; must be manually restarted after every
restart
Clock synchronization Yes
In the PLC
Master/slave
On MPI
Master/slave
S7 signaling functions
Number of stations that can be logged on for
signaling functions
16
(depends on the number of connections
configured for PG / OP and S7 basic
communication)
Process diagnostics messages Yes
Simultaneously enabled interrupt S blocks
40
Testing and commissioning functions
Status/control variables Yes
Variables
Inputs, outputs, memory bits, DBs, timers,
counters