Technical specifications
5.5 Climatic ambient conditions
Comfort Panels INOX PCT
38 Compact Operating Instructions, 05/2018, A5E38804191-AA
The following information applies to a device installed according to the specifications in these
operating instructions.
The device was tested based on IEC 60721-3-3 Class 3M3 with the following amendments
and limitations:
Vibration according to IEC 60068-2-6 5 ... 8.4 Hz, deflection 3.5 mm
8.4 ... 150 Hz, acceleration 1 g
Shock according to IEC 60068-2-27
2
Shock pulses within the specified range can be transferred to the display but do not impact
the functionality of the device.
Climatic ambient conditions
5.5.1
The following information applies to a device that is stored in its original packaging for longer
than two weeks.
The device meets the requirements of IEC 60721-3-1 Class 1K2.
Transport and short-term storage
The following information applies to a device that is transported in the original packaging and
weather-proof packaging, and stored from some time.
The device meets the requirements according to IEC 60721-3-2 Class 2K4 with the following
amendments and limitations:
1140 ... 660 hPa, corresponds to an elevation of -1000 to 3500 m
Pollutant concentration SO2: < 0.5 ppm; relative humidity < 60 %, no condensation
H
2
S: < 0.1 ppm; relative humidity < 60 %, no condensation
Note
If dewing has developed, wait until the HMI device has dried completely before switching it on.
Do not expose the HMI device to direct radiation from a heater.