Commissioning (hardware)
2.5 User memory concept
SIMOTION D410
42 Commissioning Manual, 02/2012
Table 2- 6 State of the non-volatile SIMOTION data after powering up (persistentDataState system
variable)
Status Meaning
FROM_RAM (1) Non-volatile SIMOTION data in the SIMOTION device is used
FROM_FILE (2) Non-volatile SIMOTION data is restored from the backup file
FROM_BACKUP (3) Non-volatile SIMOTION data is restored from the backup copy of the backup
file
INVALID (4) Data in the non-volatile SIMOTION data and in the backup file / backup copy
of backup file is invalid or non-existent/deleted.
The SIMOTION device has copied the default settings to the non-volatile
SIMOTION data and used this data to power up.