Parameter assignment / addressing
5.5 Configuring an Ethernet subnet
SIMOTION D4x5-2
134 Commissioning and Hardware Installation Manual, 02/2012
Default Ethernet addresses
The following addresses are assigned per default:
Table 5- 5 IP address assignment for a SIMOTION D4x5-2
Interface Use case Default address
Insert SIMOTION device or
HW Config
IP address:
Subnet mask:
Router address:
Automatic private IP
address
169.254.11.22
255.255.0.0
0.0.0.0
X127 P1
PN/IE
D4x5-2 as delivered IP address:
Subnet mask:
Router address:
Automatic private IP
address
169.254.11.22
255.255.0.0
0.0.0.0
Insert SIMOTION device or
HW Config
IP address:
Subnet mask:
Router address:
192.168.213.1
255.255.255.0
0.0.0.0
X120 P1
PN/IE-OP
(only for D4x5-2
DP)
D4x5-2 DP as delivered IP address:
Subnet mask:
Router address:
Automatic private IP
address
0.0.0.0
0.0.0.0
0.0.0.0
Insert SIMOTION device or
HW Config
IP address:
Subnet mask:
Router address:
192.168.2.1
255.255.255.0
0.0.0.0
X130 P1
PN/IE-NET
D4x5-2 as delivered IP address:
Subnet mask:
Router address:
0.0.0.0
0.0.0.0
0.0.0.0
Note
The IP addresses 192.168.215.240 to 192.168.215.255 are reserved for internal
communication in the SIMOTION D4x5-2 (subnet mask 255.255.255.240). When configuring
the external Ethernet interfaces (X127 P1, X120 P1 and X130 P1), make sure that the
internal addresses are not inside their network. (In IP, the network is defined as an AND link
of IP address and subnet mask.)
Note
If you want to go online via Ethernet, you have to make sure that the connection from PG/PC
to SIMOTION D4x5-2 is active. You can check this in NetPro. A description of how to switch
a connection to active again can be found in the Section Establishing the PG/PC assignment
(Page 130).