Faults and Alarms 10.99
6SE7087-6KP50 Siemens AG
12-22 Operating Instructions SIMOVERT MASTERDRIVES
Number / Alarm Cause Counter-measure
A141
Following error in
motion
The following error limit for motion was
exceeded during a traversing movement:
-Following error monitoring - in motion
(machine data 15) was entered incorrectly.
-The mechanical system cannot follow the
commands of the position controller.
-Actual position value invalid
-Incorrect optimization of the position controller
or speed controller.
-The mechanical system is sluggish or
blocked.
Effect:
The position control system is deactivated and
the drive decelerates via "deceleration time
during faults" (machine data 43).
-Check and correct the machine data.
-Check the actual position value (speed-
controlled operation); check position encoder,
evaluator module and encoder lead.
-Optimize the position controller or the speed
controller.
-Check the mechanical system.
A142
In position - timer
monitoring
The "in position - exact stop window" was not
reached within the time specified in"in position
- timer monitoring":
-In position - exact stop window (machine data
17) too small
-In position - timer monitoring (machine data
16) too short
-Position controller or speed controller not
optimized
-Mechanical causes
Effect:
The position control system is deactivated.
-Check and correct the machine data.
-Optimize the position controller or speed
controller.
-Check the mechanical system.
A145
Actual-value disable
not allowed - axis
standstill
The "digital input" with the "disable actual
value" function was actuated while the roll
feed was running.
Effect:
The axis movement is stopped via the
deceleration ramp, the "disable actual value"
function is not executed.
The "digital input" for "disable actual value"
can only be actuated when the axis is
stationary.
A146
Direction of movement
not allowed
A positioning movement was aborted. When
attempting to resume the movement at the
point of interruption, the roll feed would have
had to travel in the opposite direction to reach
the programmed target position. This is
inhibited by the setting of machine data 37
"response after abort".
There are various possible reasons for the
axis crossing the target position when a
positioning movement is aborted:
-Motor coastdown
-The axis was moved intentionally, e.g. in
setup mode.
Effect:
The axis movement is inhibited.
Move the axis in front of the target position in
setup mode before continuing.

Other manuals for Siemens simovert masterdrives

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simovert masterdrives and is the answer not in the manual?

Siemens simovert masterdrives Specifications

General IconGeneral
BrandSiemens
Modelsimovert masterdrives
CategoryDC Drives
LanguageEnglish

Related product manuals