Faults and Alarms 10.99
6SE7087-6KP50 Siemens AG
12-34 Operating Instructions SIMOVERT MASTERDRIVES
Number / Alarm Cause Counter-measure
A244
Travel table 3 not valid
Travel table 3 has not been correctly adopted
or has been reset.
Consequence:
Travel table 3 cannot be processed.
Adopt travel table 3 again.
Note:
Travel table 3 can only be newly adopted if it is
not selected. When travel table 3 has been
successfully adopted, the alarm message is
automatically canceled.
A245
Travel table 4 not valid
Travel table 4 has not been correctly adopted
or has been reset.
Consequence:
Travel table 4 cannot be processed.
Adopt travel table 4 again.
Note:
Travel table 4 can only be newly adopted if it is
not selected. When travel table 4 has been
successfully adopted, the alarm message is
automatically canceled.
A246
Travel table 5 not valid
Travel table 5 has not been correctly adopted
or has been reset.
Consequence:
Travel table 5 cannot be processed.
Adopt travel table 5 again.
Note:
Travel table 5 can only be newly adopted if it is
not selected. When travel table 5 has been
successfully adopted, the alarm message is
automatically canceled.
A247
Travel table 6 not valid
Travel table 6 has not been correctly adopted
or has been reset.
Consequence:
Travel table 6 cannot be processed.
Adopt travel table 6 again.
Note:
Travel table 6 can only be newly adopted if it is
not selected. When travel table 6 has been
successfully adopted, the alarm message is
automatically canceled.
A248
Travel table 7 not valid
Travel table 7 has not been correctly adopted
or has been reset.
Consequence:
Travel table 7 cannot be processed.
Adopt travel table 7 again.
Note:
Travel table 7 can only be newly adopted if it is
not selected. When travel table 7 has been
successfully adopted, the alarm message is
automatically canceled.
A249
Travel table 8 not valid
Travel table 8 has not been correctly adopted
or has been reset.
Consequence:
Travel table 8 cannot be processed.
Adopt travel table 8 again.
Note:
Travel table 8 can only be newly adopted if it is
not selected. When travel table 8 has been
successfully adopted, the alarm message is
automatically canceled.
Table 12-2 Alarm numbers, causes and their counter-measures

Other manuals for Siemens simovert masterdrives

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simovert masterdrives and is the answer not in the manual?

Siemens simovert masterdrives Specifications

General IconGeneral
BrandSiemens
Modelsimovert masterdrives
CategoryDC Drives
LanguageEnglish

Related product manuals