Parameterization 10.99
6SE7087-6KP50 Siemens AG
8-4 Operating Instructions SIMOVERT MASTERDRIVES
The following example shows the individual operator control steps to be
carried out on the PMU for a parameter reset to factory setting.
P
É Ë
P053
É Ë
É Ë
Set P053 to 0002 and grant parameter access via PMU
P
É Ë
0000 0001 0002 P053
É Ë
P053
Select P060
P060
P
É Ë
P060
Set P060 to 0002 and select "Fixed settings" menu
1
Select P970
P
É Ë
P970
Set P970 to 0000 and start parameter reset
1
P
É Ë
2 P060
É Ë
P
É Ë
0 °005
É Ë
É Ë
P060 P970
...
Example