10.99 Faults and Alarms
Siemens AG 6SE7087-6KP50
SIMOVERT MASTERDRIVES Operating Instructions 12-17
Number / Alarm Cause Counter-measure
A084
CB alarm
The following description refers to the 1st
CBP. For other CBs or the TB see the
operating instructions for the CB board.
The telegram traffic between the DP master
and the CBP has been interrupted (e.g. cable
break, bus cable pulled out or DP master
powered down).
Consequence:
If P722 (P695) is not equal to zero, this will
cause the fault message F082 to be tripped.
A085
CB alarm
The following description refers to the 1st
CBP. For other CBs or the TB see the
operating instructions for the CB board.
The CBP does not generate this alarm!
A086
CB alarm
The following description refers to the 1st
CBP. For other CBs or the TB see the
operating instructions for the CB board.
Failure of the heart-beat counter on the basic
unit. The heartbeat counter on the basic unit is
no longer being incremented. The
communication between the CBP and the
basic board is disturbed.
A087
CB alarm
The following description refers to the 1st
CBP. For other CBs or the TB see the
operating instructions for the CB board.
Fault in the DPS manager software of the
CBP.
A088
CB alarm
See user manual for CB board
A089
CB alarm
See user manual for CB board
Alarm of the 2nd CB board corresponds to
A81 of the 1st CB board
A090
CB alarm
See user manual for CB board
Alarm of the 2nd CB board corresponds to
A82 of the 1st CB board
A091
CB alarm
See user manual for CB board
Alarm of the 2nd CB board corresponds to
A83 of the 1st CB board
A092
CB alarm
See user manual for CB board
Alarm of the 2nd CB board corresponds to
A84 of the 1st CB board
A093
CB alarm
See user manual for CB board
Alarm of the 2nd CB board corresponds to
A85 of the 1st CB board
A094
CB alarm
See user manual for CB board
Alarm of the 2nd CB board corresponds to
A86 of the 1st CB board
A095
CB alarm
Alarm of the 2nd CB board. Corresponds to
A87 of the 1st CB board
See user manual for CB board
A096
CB alarm
See user manual for CB board
Alarm of the 2nd CB board corresponds to
A88 of the 1st CB board
A097
TB alarm 1
not Compact PLUS
See user manual for TB board

Other manuals for Siemens simovert masterdrives

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simovert masterdrives and is the answer not in the manual?

Siemens simovert masterdrives Specifications

General IconGeneral
BrandSiemens
Modelsimovert masterdrives
CategoryDC Drives
LanguageEnglish

Related product manuals