Installing
3.2 EMC-compliant installation of a machine or system
Power Module PM240P-2
22 Hardware Installation Manual, 06/2020, A5E37800827C AD
Cable routing inside the cabinet
Route the power cables with a high level of interference so that there is a minimum
clearance of 25 cm to cables with a low level of interference.
If the minimum clearance of 25 cm is not possible, insert separating metal sheets
between the cables with a high level of interference and cables with a low level of
interference. Connect these separating metal sheets to the mounting plate to establish a
good electrical connection.
Cables with a high level of interference and cables with a low level of interference may
only cross over at right angles:
Keep all of the cables as short as possible.
Route all of the cables close to the mounting plates or cabinet frames.
Route signal and data cables - as well as the associated equipotential bonding cables -
parallel and close to one another.
Twist incoming and outgoing unshielded individual conductors.
Alternatively, you can route incoming and outgoing conductors in parallel, but close to
one another.
Ground any unused conductors of signal and data cables at both ends.
Signal and data cables must only enter the cabinet from one side, e.g. from below.
Use shielded cables for the following connections:
Cable between the converter and line filter
Cable between the converter and output reactor or sine-wave filter
Figure 3-3 Routing converter cables inside and outside a control cabinet