EasyManua.ls Logo

Siemens SINAMICS G120 PM240P-2 - Specific Data, 400 V Converters

Siemens SINAMICS G120 PM240P-2
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
6.4 400 V converters
Power Module PM240P-2
60 Hardware Installation Manual, 06/2020, A5E37800827C AD
6.4.2 Specific data, 400 V converters
The fuses listed in the following tables are examples of suitable fuses.
You can find additional suitable fuses in the Internet:
Branch protection and short-circuit strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
Table 6- 1 PM240P-2, IP20, Frame Size D, 3-ph. AC 380 V … 480 V
Article number without filter
Article number with filter
6SL3210-1RE24-5UL0
6SL3210-1RE24-5AL0
6SL3210-1RE26-0UL0
6SL3210-1RE26-0AL0
6SL3210-1RE27-5UL0
6SL3210-1RE27-5AL0
LO base load power 22 kW 30 kW 37 kW
LO base load input current 42 A 57 A 70 A
LO base load output current 45 A 60 A 75 A
HO base load power
18.5 kW
22 kW
30 kW
HO base load input current
38 A
47 A
62 A
HO base load output current 38 A 45 A 60 A
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NE1820-0 / 80 A
70 A
3NE1021-0 / 100 A
90 A
3NE1021-0 / 100 A
100 A
Power loss without filter
0.68 kW
0.76 kW
1.01 kW
Power loss with filter
0.68 kW
0.77 kW
1.02 kW
Required cooling air flow
55 l/s
55 l/s
55 l/s
Weight without filter
16.6 kg
18.3 kg
18.3 kg
Weight with filter
18.3 kg
19 kg
19 kg
Table 6- 2 PM240P-2, IP20, Frame Size E, 3-ph. AC 380 V … 480 V
Article number without filter
Article number with filter
6SL3210-1RE28-8UL0
6SL3210-1RE28-8AL0
6SL3210-1RE31-1UL0
6SL3210-1RE31-1AL0
LO base load power
45 kW
55 kW
LO base load input current
86 A
104 A
LO base load output current
90 A
110 A
HO base load power
37 kW
45 kW
HO base load input current
78 A
94 A
HO base load output current
75 A
90 A
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NE1022-0 / 125 A
125 A
3NE1224-0 / 160 A
150 A
Power loss without filter 1.19 kW 1.54 kW
Power loss with filter 1.2 kW 1.55 kW
Required cooling air flow
83 l/s
83 l/s
Weight without filter
26.4 kg
26.4 kg
Weight with filter 28.4 kg 28.4 kg

Table of Contents