Technical data
6.5 690 V converters
Power Module PM240P-2
64 Hardware Installation Manual, 06/2020, A5E37800827C AD
6.5.2 Specific data, 690 V converters
The fuses listed in the following tables are examples of suitable fuses.
You can find additional suitable fuses in the Internet:
Branch protection and short-circuit strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
Table 6- 5 PM240P-2, IP20, frame size D, 3 AC 500 V … 690 V
Article number without filter
Article number with filter
6SL3210-1RH21-4UL0
6SL3210-1RH21-4AL0
6SL3210-1RH22-0UL0
6SL3210-1RH22-0AL0
6SL3210-1RH22-3UL0
6SL3210-1RH22-3AL0
LO base load power 11 kW 15 kW 18.5 kW
LO base load input current 14 A 18 A 22 A
LO base load output current 14 A 19 A 23 A
HO base load input current
HO base load output current 11 A 14 A 19 A
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NE1815-0 / 25 A
3NE1815-0 / 25 A
3NE1803-0 / 35 A
Required cooling air flow
Table 6- 6 PM240P-2, IP20, frame size D, 3 AC 500 V … 690 V
Article number without filter
Article number with filter
6SL3210-1RH22-7UL0
6SL3210-1RH22-7AL0
6SL3210-1RH23-5UL0
6SL3210-1RH23-5AL0
6SL3210-1RH24-2UL0
6SL3210-1RH24-2AL0
LO base load input current
LO base load output current
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
3NE1803-0 / 35 A
3NE1817-0 / 50 A
3NE1818-0 / 63 A
Power loss without filter 0.56 kW 0.72 kW 0.88 kW
Power loss with filter 0.56 kW 0.73 kW 0.88 kW
Required cooling air flow 55 l/s 55 l/s 55 l/s