Spare parts and accessories
7.2 Optional accessories
Power Module PM240P-2
Hardware Installation Manual, 06/2020, A5E37800827C AD
83
Connecting the Brake Relay to the converter
The connector for the Brake Relay is located at the front of the Power Module. Lay the cable
harness for the Brake Relay in the cable routing.
7.2.3 Line harmonics filter
The line harmonics filters reshape the distorted current back to the desired sinusoidal
waveform.
With the line harmonics filters the converter fulfills the IEEE 519 standards.
For technical details refer to the following link:
Line harmonics filters
(https://www.schaffner.com/products/download/product/datasheet/fn-3440-ecosine-50hz-
passive-harmonic-filters/)
Note
If you use a line harmonics filter the permissible line voltage is 380
V ... 415 V 3 AC ±10 %
instead of 380
V ... 480 V 3 AC ± 10 % without a line harmonics filter.