Accessories
7.3 Braking Resistor
Power Module PM240
Hardware Installation Manual, 07/2009, A5E00807525B AD
111
Table 7- 24 Dimension data: Braking resistor, all data in mm and (inches), Part 1
Order No. of the braking
resistor
6SE6400-4BD16-
5CA0
6SE6400-4BD21-
2DA0
6SE6400-4BD22-
2EA0
FSC FSD FSE Suitable for Power Module
(HO)
5.5 kW ... 11 kW 15 kW ... 22 kW 30 kW ... 37 kW
Order-No. of the suitable
Power Module
6SL3224-0BE25-5 .
A0
6SL3224-0BE27-5 .
A0
6SL3224-0BE31-1 .
A0
6SL3224-0BE31-5 .
A0
6SL3224-0BE31-8 .
A0
6SL3224-0BE32-2 .
A0
6SL3224-0BE33-0 .
A0
6SL3224-0BE33-7 .
A0
L 285 (11.22) 515 (20.27) 645 (25.39)
L1 200 (7.87) 350 (13.77) 480 (18.89)
L2 145 (5.70) 205 (8.07) 205 (8.07)
L3 170 (6.69) 195 (7.67) 195 (7.67)
D 150 (5.90) 175 (6.88) 175 (6.88)
D1 217 (8.54) 242 (9.52) 242 (9.52)
D2 185 (7.28) 210 (8.26) 210 (8.26)
W 185 (7.28) 270 (10.62) 270 (10.62)
W1 230 (9.05) 315 (12.40) 315 (12.40)
Table 7- 25 Dimension data: Braking resistor, all data in mm and (inches), Part 2
Order No. of the braking
resistor
6SE6400-4BD24-0FA0 6SE6400-4BD26-0FA0
FSF Suitable for Power Module
(HO)
45 kW ... 75 kW 90 kW ... 110 kW
Order-No. of the suitable
Power Module
6SL3224-0BE34-5 . A0
6SL3224-0BE35-5 . A0
6SL3224-0BE37-5 . A0
6SL3224-0BE38-8UA0
6SL3224-0BE41-1UA0
L 650 (25.59) 526 (20.71)
L1 510 (20.07) -
L2 270 (10.62) 380 (14.96)
L3 335 (13.18) 500 (19.69)
D 315 (12.40) 301 (11.85)
D1 382 (15.03) -
D2 382 (15.03) -
W 400 (15.74) 483 (19.09)
W1 435 (17.12) -
The braking resistors can be installed horizontally or vertically. The connections on vertically
installed resistors must be at the bottom.
The braking resistor can be positioned outside the cabinet or switchgear room. This enables
the resulting heat loss around the Power Modules to be dissipated. This reduces the level of
air conditioning required.