Power Module PM240
Hardware Installation Manual, 07/2009, A5E00807525B AD
65
Technical specifications
6
Common performance ratings of the Power Module
Table 6- 1 Performance ratings
Feature Specification
Line operating voltage 3 AC 380 V … 480 V ± 10%
The permissible voltage depends on the operational altitude
Input frequency 47 Hz … 63 Hz
Power factor λ 0.7 ... 0.85
1.5 x Base-load output current (150% overload) for 57 s every 300 s Overload capability for
base load (HO)
0.37 kW ... 75 kW
2 x Base-load output current (200% overload) for 3 s every 300 s
1.36 x Base-load output current (136% overload) for 57 s every 300 s Overload capability for
base load (HO)
90 kW ... 200 kW
1.6 x Base-load output current (160% overload) for 3 s every 300 s
1.1 x Base-load output current (110% overload) for 57 s every 300 s Overload capability for
base load (LO)
7.5 kW ... 90 kW
1.5 x Base-load output current (150% overload) for 3 s every 300 s
1.1 x Base-load output current (136% overload) for 59 s every 300 s Overload capability for
base load (LO)
110 kW ... 250 kW
1.5 x Base-load output current (150% overload) for 1 s every 300 s
Inrush current Less than rated input current
Pulse frequency
4 kHz standard for 0.37 kW ... 75 kW (HO)
2 kHz standard for 90 kW ... 200 kW (HO)
The pulse frequency can be changed manually in 2 kHz steps.
Increasing the pulse frequencies above standard leads to an output
current reduction.
Electromagnetic
compatibility
Optional Class A filters available according to EN 55011
Braking DC braking, Compound braking, Dynamic braking with integrated chopper
Protection level IP20 or IPXXB
IPXXB protection is ensured with the Power Module FSGX
(HO 132 kW … 200 kW) in conjunction with the Control Units CU240E
and CU230P-2.
0.37 kW ... 110 kW
0 °C … +50 °C (14 °F … 122 °F)
Temperature range
without derating (HO)
132 kW ... 200 kW
0 °C … +40 °C (32 °F … 104 °F)
Temperature range
without derating (LO)
0.37 kW ... 132 kW
0 °C … +40 °C (14 °F … 104 °F)