EasyManua.ls Logo

Siemens SINAMICS G120 - DC 24 V Power Supply Connection (FSGX)

Siemens SINAMICS G120
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting
4.7 DC 24V power supply connection (FSGX)
Power Module PM240
46 Hardware Installation Manual, 07/2009, A5E00807525B AD
4.7 DC 24V power supply connection (FSGX)
-X9: Terminal block
The Power Module FSGX requires a separate DC 24V power supply. The power supply is
connected to the X9 terminal block of the Power Module.
Figure 4-4 -X9 terminal block ① on the Power Module FSGX
Table 4- 5 Terminal block -X9
Terminal Function Technical specifications
1 P24V
2 M
Voltage: 24 V DC (20.4 V - 28.8 V)
Current consumption: max. 4 A
3 Reserved, do not use
4 Reserved, do not use
5 HS1 Line contactor control
6 HS2 Line contactor control
Max. connectable cross-section: 1.5 mm²
Connection
Connect the external DC 24 V supply to terminals 1 (P 24 V) and 2 (Mext) of terminal
block -X9 on the Power Module.
NOTICE
Not connected 24V power supply lead to a fault message of the inverter as soon as the
400V power supply is disconnected from the Power Module.

Table of Contents

Other manuals for Siemens SINAMICS G120