Technical specifications
Power Module PM240
66 Hardware Installation Manual, 07/2009, A5E00807525B AD
Feature Specification
160 kW ... 250 kW
0 °C … +40 °C (32 °F … 104 °F)
Temperature range with
derating
Operational temperature up to 60° C (140° F) is possible with power
derating
Storage temperature -40 °C … +70 °C (-40 °F … 158 °F)
Humidity < 95% RH - non-condensing
In areas of high relative humidity, measures should be taken to ensure
that condensation does not form within or around the SINAMICS G120.
Anti-condensation heaters are commonly used to prevent the formation of
condensation.
Pollution According pollution degree level 2
Do not install the SINAMICS G120 in an environment which contains
atmospheric pollutants such as dust and/or corrosive gases.
Shock and vibration Do not drop the SINAMICS G120 or expose to sudden shock. Do not
install the SINAMICS G120 in an area where it is likely to be exposed to
constant vibration.
Electromagnetic radiation Do not install the SINAMICS G120 near sources of electromagnetic
radiation.
0.37 kW ... 110 kW (HO)
Up to 1000 m (3300 ft) above sea level
Operational altitude
without derating
132 kW ... 200 kW (HO)
Up to 2000 m (6500 ft) above sea level
Operational altitude with
derating
Higher operational altitude is possible with power derating