EasyManua.ls Logo

Siemens SINAMICS G120 - Page 67

Siemens SINAMICS G120
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
Power Module PM240
Hardware Installation Manual, 07/2009, A5E00807525B AD
67
Relationship between pulse frequency and output base-load current reduction
Table 6- 2 Current reduction depending on pulse frequency
Output base-load current at pulse frequency of
LO base
load
2 kHz 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz 14 kHz 16 kHz
kW A A A A A A A A
0.37 -- 1.30 1.11 0.91 0.78 0.65 0.59 0.52
0.55 -- 1.70 1.45 1.19 1.02 0.85 0.77 0.68
0.75 -- 2.20 1.87 1.54 1.32 1.10 0.99 0.88
1.1 -- 3.10 2.64 2.17 1.86 1.55 1.40 1.24
1.5 -- 4.10 3.49 2.87 2.46 2.05 1.85 1.64
2.2 -- 5.90 5.02 4.13 3.54 2.95 2.66 2.36
3.0 -- 7.70 6.55 5.39 4.62 3.85 3.47 3.08
4.0 -- 10.20 8.67 7.14 6.12 5.10 4.59 4.08
7.5 -- 18.00 16.20 13.30 11.40 9.50 8.60 7.60
11.0 -- 25.00 22.10 18.20 15.60 13.00 11.70 10.40
15.0 -- 32.00 27.20 22.40 19.20 16.00 14.40 12.80
18.5 -- 38.00 32.30 26.60 22.80 19.00 17.10 15.20
22 -- 45.00 38.25 31.50 27.00 22.50 20.25 18.00
30 -- 60.00 52.70 43.40 37.20 31.00 27.90 24.80
37 -- 75.00 63.75 52.50 45.00 37.50 33.75 30.00
45 -- 90.00 76.50 63.00 54.00 45.00 40.50 36.00
55 -- 110.0 93.50 77.00 -- -- -- --
75 -- 145.0 123.3 101.5 -- -- -- --
90 -- 178.0 151.3 124.6 -- -- -- --
110 205.0 178.0 -- -- -- -- -- --
132 250.0 205.0 -- -- -- -- -- --
160 302.0 250.0 -- -- -- -- -- --
200 370.0 302.0 -- -- -- -- -- --
250 477.0 370.0 -- -- -- -- -- --

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals