4.10 ESD guidelines
Power Module PM240
50 Hardware Installation Manual, 07/2009, A5E00807525B AD
Screening without a Screen Termination Kit
In order to meet radiated emissions a screen termination kit must be used. Screening without
a screen termination kit is only suitable for installation in a metal cabinet.
Should a Screen Termination Kit not be available, the inverter then can be screened using
the methodology shown in the figure below. This diagram shows both methodologies of
screening.
Note
The EMI illustration below is not to scale. The terminal cover on Frame Size D cannot be
removed. It has been removed to show the correct cable connection for the terminals.









Line power input
Motor cable
Metal back plate
Use suitable clips to fix motor and power cable screen securely to metal back plate
Screen cables
Screen Termination Kit
Gromments
Figure 4-7 Example of wiring to minimize the effect of EMI