EasyManua.ls Logo

Siemens SINAMICS G120 - Page 81

Siemens SINAMICS G120
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Accessories
7.1 Reactor and filter
Power Module PM240
Hardware Installation Manual, 07/2009, A5E00807525B AD
81
Table 7- 2 Technical specifications of the line reactors (table 1 of 6)
Suitable for Power Module with rated power (HO) of
0.37 kW ... 0.55 kW 0.75 kW ... 1.1 kW 1.5 kW
Feature
FSA
MLFB of the line reactor 6SE6400-3CC00-2AD3 6SE6400-3CC00-4AD3 6SE6400-3CC00-6AD3
MLFB of the suitable Power
Module
6SL3224-0BE13-7UA0
6SL3224-0BE15-5UA0
6SL3224-0BE17-5UA0
6SL3224-0BE21-1UA0
6SL3224-0BE21-5UA0
Inductance 11.5 mH 6.3 mH 3.2 mH
Power loss at 50/60 Hz 6/7 W 12.5/15 W 7.5/9 W
Line connection Screw terminals 1 … 2.5 mm²
Connection to Power
Module
Cable, 380 mm length
Degree of protection IP20
Overall dimensions
Width
Height
Depth
75.5 mm
200 mm
50 mm
Fixing dimensions
Width
Height
187 mm
56 mm
Fixing screw 4 × M4
Weight 0.6 kg 0.8 kg 0.6 kg
Possible as base
component
yes
Table 7- 3 Technical specifications of the line reactors (table 2 of 6)
Suitable for Power Module with rated power (HO) of
2.2 kW ... 3 kW 4 kW 5.5 kW ... 7.5 kW
Feature
FSB FSC
MLFB of the line reactor 6SL3203-0CD21-0AA0 6SL3203-0CD21-4AA0 6SL3203-0CD22-2AA0
MLFB of the suitable Power
Module
6SL3224-0BE22-2 . A0
6SL3224-0BE23-0 . A0
6SL3224-0BE24-0 . A0 6SL3224-0BE25-5 . A0
6SL3224-0BE27-5 . A0
Inductance 2.2 mH 1.3 mH 0.56 mH
Power loss at 50/60 Hz 9/11 W 27/32 W 98/118 W
Line connection Screw terminals 1.5 … 6 mm² Screw terminals
2.5 … 10 mm²
Connection to Power
Module
Cable, 460 mm length Cable, 490 mm length
Degree of protection IP20
Overall dimensions
Width
Height
Depth
153 mm
290 mm
70 mm
189 mm
371 mm
50 mm

Table of Contents

Other manuals for Siemens SINAMICS G120

Related product manuals