Accessories
7.1 Reactor and filter
Power Module PM240
90 Hardware Installation Manual, 07/2009, A5E00807525B AD
Installing the output reactor as lateral mounting component
The output reactors for Power Modules with a rated power (HO) of more than 11 kW have to
be mounted laterally.
0RXQWLQJ
VXUIDFHRU
FDELQHWZDOO
/LQH
0RWRU
2XWSXWUHDFWRU
8 9 : 3(
3(:98
8
9
:
3(
0
3RZHU0RGXOH
8 9 : 3(
8 9 : 3(
Figure 7-7 Connecting the output reactor as lateral component
For more information see http://support.automation.siemens.com/WW/view/en/22103628
Technical specifications of the output reactors
The major electrical specification of the output reactors is the same as for the suitable Power
Module. This applies to:
voltage
rated current
The maximum permissible output frequency of the Power Module is 150 Hz when an output
reactor is used – the pulse frequency must not exceed 4 kHz.
The admissible ambient conditions of the output reactors are the same as for the suitable
Power Module. This applies to:
storage and transport temperature
operating temperature
relative humidity
shock and vibration load