Accessories
7.1 Reactor and filter
Power Module PM240
96 Hardware Installation Manual, 07/2009, A5E00807525B AD
Installing the sine-wave filter as lateral mounting component
The sine-wave filter for Power Modules with a rated power (HO) of more than 11 kW has to
be mounted laterally.
0RXQWLQJ
VXUIDFHRU
FDELQHWZDOO
/LQH
0RWRU
6LQHZDYHILOWHU
8
9
:
3(
0
3RZHU0RGXOH
8 9 : 3(
8 9 : 3(
8 9 : 3(
3(:98
Figure 7-9 Connecting the sine-wave filter as lateral component
For more information see http://support.automation.siemens.com/WW/view/en/29522775
Technical specifications of the sine-wave filter
The major electrical specification of the sine-wave filter is the same as for the suitable Power
Module. This applies to:
voltage
current
The maximum permissible output frequency of the Power Module is 150 Hz when a sine-
wave filter is used – the pulse frequency must not exceed 8 kHz.
The admissible ambient conditions of the sine-wave filter are the same as for the suitable
Power Module. This applies to:
storage and transport temperature
operating temperature
relative humidity
shock and vibration load