Setting parameters with the BOP20
4.5 Important functions via BOP20
Basic Operator Panel 20 (BOP20)
Operating Instructions, 11/2017, A5E00809375A
29
Restore the factory settings
The factory setting of the complete device can be restored in the CU drive object.
p0009 = 30
p0976 = 1
Copy from RAM to ROM
You can initiate the saving of all parameters to the non-volatile memory (memory card) in the
drive object CU:
Press the "P" key for 3 seconds or
p0977 = 1
Note
Parameter rejection with active identification
This parameter is not accepted if an identification routine (e.g. motor identification routine)
has been selected on a drive.
Identification via LED
The main component of a drive object (e.g. power section) can be identified using the index
of p0124. The ready LED on the module starts to flash. The index corresponds to the index
in p0107; the drive object type can be identified using this parameter.
The drive objects can be identified using the following parameters:
p0124 Power unit detection via LED
p0144 Voltage Sensing Module detection via LED
p0144 Sensor Module detection via LED
p0154 DRIVE-CLiQ hub identification using LED
p0154 Terminal Module detection via LED
Acknowledge error
All errors whose cause has been rectified can be acknowledged by pressing the Fn key.