Display messages
05/2020, 4BS0576F-004
9
Text for event memory entry
1004 Switch interlock active - The FI is in the start-inhibiting status. Set the OFF1-command or set pa-
rameter "P-INV. BEHVIOUR:Switch interlock" to "off " (for operation via
field bus however there is always an OFF1-command required )
1006 !! Emergency stop !! Operation - Actually, an emergency stop command is set. Reset the emergency stop
and then acknowledge the inverter.
1007 T1 of
P-OPERATION/P-Off2
(NC)
T2 of
P-OPERATION/P-Off2 (NC)
- An OFF2-command is set. Reset the OFF2-command and then
acknowledge the inverter.
The default text is !! OFF2 !! Operation, however, can be parameterized
absolutely free.
1108 mains off - Voltage supply for power section missing resp. faulty. Check the main
supply resp. the mains fuses.
1109 System Mains off - Voltage supply for power section missing resp. faulty. Check the main
supply resp. the mains fuses.
2004 Fault S1:3 not off - Switch off S1:3 (under grey cover)
2023 ! Parameter fault ! Pole pair=0 n-/f-Mot - The ratio of the parameters n-motor to f-motor in menu "P-MACHINE
POWER CONV/P-motor data"
is not plausible regarding number of pairs of
poles (pair of poles = 0). Adjust parameter "n-motor" or "f-motor".
2024 ! Parameter fault ! Alloc.: n/f-Mot SYN - The ratio of the parameters n-motor to f-motor in menu "P-MACHINE
POWER CONV/P-motor data" is not plausible. The number of pairs of
poles cannot be calculated. Adjust parameter "n-motor" or "f-motor".
2025 ! Parameter fault ! Alloc.: n/f-Mot ASM - The ratio of the parameters n-motor to f-motor in menu "P-MACHINE
POWER CONV/P-motor data" is not plausible. Parameter "n-motor" devi-
ates widely from the synchronous speed. Adjust parameter "n-motor" or
"f-motor".
2027 ! Parameter fault ! R-BrakingRes.too low - Use a brake resistor with a higher resistance value (see technical data)
and parameterize it, otherwise the brake transistor might be destroyed.
2036 Linkage too long circle - Too many operator functions (e.g. signal generators MLD or self-holding
functions) have been connected in line (max. 3). or operator functions were
connected in a loop (e.g. input of a self-holding function with its output).
Change parameter setting.