Requirements
Data Backup of SINAMICS S120
SINAMICS S120 at Technology CPU Entry ID: 21767896
V1.0 Edition 10/28/05 27/58
Copyright © Siemens AG 2005 All rights reserved
SINAMICS S120 und Technologie-CPU V2.0-SP1__05-10-28_13-20_e.doc
Recovery of the backed up data
The data backed up in one of the three parameter files can be loaded back
to the RAM of SINAMICS S120 analog to the data backup using the
parameters p9 and p976.
Table 4-2 Loading the backed up drive data from the compact flash card
No. Instruction Note
1.
In the Project menu, establish the
online connection to SINAMICS
S120 by selecting the menu item
Connect to target system.
2.
Via the context menu of the CU320
control unit, call the Expert list of
the parameters of SINAMICS S120.
3.
In the expert list, select parameter
p9.
4.
Click in the input box for the
parameter value to call the list for
the input options.
Select the Parameter Reset (30)
setting.