EasyManua.ls Logo

Siemens SINAMICS SL150 - Page 63

Siemens SINAMICS SL150
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Attach the cable shield to a shield busbar directly after the line inlet into the cabinet. Insulate
the shielded cable without any interruptions. Route the cable shield up to the device
connection.
Shield busbar
Shielded cable
Mounting clip
Figure 6-1 Shield connection using a clip
NOTICE
Damaged or incorrectly mounted cable shielding
Incorrect connection or damaging of the cable shield can impair the function of the system.
Handle the cable shield carefully.
Ensure that the cable shield is correctly connected.
Bridge shield gaps (at terminals, circuit-breakers, contactors, etc.) with minimum
impedance and through the largest possible surface area.
Shield busbars
Cables
Terminals
Figure 6-2 Bridging shield gaps
Electrical connection
6.3 Electromagnetic compatibility
SINAMICS SL150 6SL38600UL432AA0Z
Operating Instructions Rev.201910281433 EXAMPLE 63

Table of Contents

Other manuals for Siemens SINAMICS SL150

Related product manuals