SINUMERIK 840D/840Di/810D Diagnostics Guide (DA) – 11.02 Edition
4182 Channel %1 invalid M auxiliary function number in %2%3, MD reset
Parameters: %1 = Channel number
%2 = MD identifier
%3 = If required, MD index
Definitions: In the specified machine data, a number has been specified for the configuration of an M
function which is occupied by the system, and cannot be used for an assignment. (M0 to
M5, M17, M30, M40 to M45 and also M98, M99 with applied ISO dialect). The value set
by the user has been reset to the default value by the system.
Reactions: - Alarm display.
- Interface signals are set.
- Mode group not ready.
- Channel not ready.
- NC Start disable in this channel.
- NC Stop on alarm.
Remedy: Configure an M function in the specified machine data which is not occupied by the sys-
tem (M0 to M5, M17, M30, M40 to M45 and also M98, M99 with applied ISO dialect).
Program Continuation: Clear alarm with the RESET key. Restart part program
4183 Channel %1 M auxiliary function number %2 used several times (%3 and %4)
Parameters: %1 = Channel number
%2 = M auxiliary function number
%3 = MD identifier
%4 = MD identifier
Definitions: In the specified machine data, a number has been used several times for the configura-
tion of an M function.
Reactions: - Alarm display.
- Interface signals are set.
- Mode group not ready.
- Channel not ready.
- NC Start disable in this channel.
- NC Stop on alarm.
Remedy: Check the specified machine data and create a unique assignment of M auxiliary function
numbers.
Program Continuation: Switch control OFF - ON.
4184 Channel %1 illegally predefined auxiliary function in %2%3, MD reset
Parameters: %1 = Channel number
%2 = MD identifier
%3 = If required, MD index
Definitions: In the specified machine data, a predefined auxiliary function has been illegally config-
ured.
The value set by the user has been reset to the default value by the system.
Reactions: - Mode group not ready.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Remedy: Configure a valid value in the specified machine data.
Program Continuation: Clear alarm with the RESET key. Restart part program