08/2005 Overview of Alarms
2-83
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Remedy: Please inform the authorized personnel/service department. Do not use rapid interrupt
inputs or contact the machine manufacturer with a view to retrofitting this option!
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
8010 Option 'activation of more than %1 axes' not set
Parameters: %1 = Number of axes
Definitions: More machine axes have been defined through the channel-specific MD 20070
AXCONF_MACHAX_USED than are allowed in the system.
Reactions: - NC not ready.
- Mode group not ready, also effective for single axes
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department. The sum of all axes that
have been configured through the channel-specific MD 20070
AXCONF_MACHAX_USED, must not exceed the maximum number of axes (dependent
on configuration -> option, basic version: 4 axes).
Program Con-
tinuation:
Switch control OFF - ON.
8020 Option 'activation of more than %1 channels' not set
Parameters: %1 = Number of channels
Definitions: A 2nd channel has been indicated but the corresponding option does not exist.
Reactions: - NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
Remedy: In the system-specific MD 10010 ASSIGN_CHAN_TO_MODE_GROUP, reduce the num-
ber of channels to 1 or retrofit the option for a 2nd channel.
Program Con-
tinuation:
Switch control OFF - ON.
8021 Option 'activation of more than %1 mode groups' not set
Parameters: %1 = Number of mode groups
Definitions: The option for the number of mode groups is not compatible with the activated mode
group.
Reactions: - NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
Remedy: Add option for more mode groups. Activate fewer mode groups.
Program Con-
tinuation:
Switch control OFF - ON.
8022 Option 'activation of more than %1KB SRAM' not set
Parameters: %1 = Memory size
Definitions: The option for memory extension does not correspond to the active SRAM.
Reactions: - NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
Remedy: Please inform the authorized personnel/service department.