3 Operation
3.3 Configuring Mode (Parameterization and Configuring Mode)
3.3.2 Parameterization Mode AdAP (Adaptation)
SIP ART DR24 6DR2410
C79000-G7476-C153-03
143
D Adaptation error messages
no exit manual mode during adaptation ⇒
MAnual
YbL direction--dependent blocking operation via
MoDE the control signals ⇒
n Tracking mode via the control signals ⇒
MoDE
ovEr > 10 % overshoot of the transient function
Shot
⇒ accurate adaptation not possible
too because of too small a line time constant
FAST accurate adaptation not possible
Pv x outside the measuring span 0 to 100 % ⇒
oFL
no at 67 % tU full scale value not reached
End
⇒ tU too short
⇒ loop cannot reach full scale value,
e.g. integrally active line
⇒ transient recovery time t
95
> 12 h
too x after 50 % tU still within starting band
SMAL
⇒ tU too short
⇒ y step too small
ALL step response in wrong direction within
PASS 30 % tU
⇒ Change active direction of the controller
⇒ control loop undershoot (all pass loop),
all--pass loops not defined among
loop models
Y y outside the measuring span of 0 to 100% ⇒
oFL
no after expiry of Ty the y step has not been
dY performed correctly for the S-controller ⇒
Error
message Explanation
dd1 dd2
y
Manual
Δy too big or too small
Check position feedback and drive of the
final control element
y
Manual
Δy too big or too small
(transient recovery time t
95
<5s)
cancel mode of operation
-10 0
y
%tU
not not stable at 10 % tU after
StAt start of adaptation
⇒ wait and restart adaptation
-10 0
y
%tU
30
100
x, y
x, y
100
-10 0
y
%tU
50
100
x, y
-10 0
y
&tU
67
100
x, y
-10 0
y
%tU
67
100
x, y
Table 3-2 Adaptation error messages