1 Technical Description
1.5 Functional Description
1.5.8 Complex Functions (Arithmetic blocks c, d, h)
Manual
62
SIP ART DR24 6DR2410
C79000-G7476-C153-03
are ignored
t
t
E
A
td
T
Blocking
td
Figure 1--28 Timing function, dead time element
Restart conditions:
Power on Band B
bAtt = no 0.000, until td runs out
bAtt = YES last value until td runs out
(hdEF)
Function transmitter FUL1, FUL2, FUL3 (linear)
E
A
ncon
Vertex 00, 20, 40, 60, 80, 100
A
E
.A
c.F
--
.1
n
---
FUL1, FUL2, FUL3
(oFPA)
The function transmitter assigns every value of the input variable E in the range from 0 % to
+100 % an output variable A in the range from --199.9 % to +199.9 % by means of the function
entered by the user: A = F(E). The function is entered by the private parameters „vertex 00 to
100 for 0 % to +100 % E in 20% steps. The function is continued linearly when E overmodu-
lates.
The output function is formed by linear sections between the vertexes.
The function transmitters can be used for example for parameter control in the controller func-
tion blocks h*.F.

Table of Contents

Other manuals for Siemens SIPART DR22

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART DR22 and is the answer not in the manual?

Siemens SIPART DR22 Specifications

General IconGeneral
BrandSiemens
ModelSIPART DR22
CategoryController
LanguageEnglish

Related product manuals