Voltage-Sum Supervision
Setting Values
Threshold 0.300 V to 170.000 V Increments of 0.001 V
Delay failure indication 0.00 s to 100.00 s Increments of 0.01 s
Dropout Ratio
Dropout ratio Approx. 0.97
Times
Tripping time Approx. 500 ms
Dropout time Approx. 500 ms
11.25
Technical Data
11.25 Voltage-Sum Supervision
SIPROTEC 5, Low-Impedance Busbar Protection, Manual 975
C53000-G5040-C019-C, Edition 04.2021