EasyManua.ls Logo

Siemens SIPROTEC 7ST61 - Page 56

Siemens SIPROTEC 7ST61
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data type definitions
56
SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
Indication type (bits 4 and 5)
01
bin
= 1
hex
for single-point indications
10
bin
= 2
hex
for double-point indications
The bits designated as "reserved = 0" are at present always transmitted with the
value = 0. These bit positions are not to be evaluated by the PROFIBUS-DP master,
as in future, further information is envisaged to be transmitted therein.
Example A change from ON to OFF of the indicated single-point indication used in the
example for the identification byte (see above) is transmitted with the value byte
00010000
bin
= 10
hex
.
Bytes 3 to 10:
Time stamp
The absolute time stamp is transmitted with the data indicated in Figure 3-9 (millisec-
onds up to year) for the point in time at which the alarm changed state.
Meaning of the clock status:
Logic OR-combination of the real time status bits:
10
hex
set: daylight saving summer time
20
hex
set: real time clock error
40
hex
set: real time clock not valid

Table of Contents