Selection tables 400 V AC
3.1 Motor starter protector + contactor
Configuring SIRIUS Innovations
26 Configuration Manual, 04/2010, A8E56203880102-02
Standard three-phase motor
4-pole at 400 V AC
1)
Standard output P Motor current
(guide value) I
Setting range
Overload release
Motor starter
protector
Motor starter
protector Motor
protection
Contactor
2)
kW A A Order No. Order No.
Size
Short-circuit breaking capacity I
q
= 55 kA
18,5
3)
35 30 ... 36 3RV2021-4PA10 3RT1035-1AP00 S0/S2
18,5
3)
35 34 ... 40 3RV2021-4FA10 3RT1035-1AP00 S0/S2
Order numbers for basic versions with screw terminals and spring-loaded terminals also possible.
1)
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
2)
Rated control supply voltage 230 V AC, 50 Hz, other control voltages possible.
3)
Discrete mounting only, without a link module.