Selection tables 500 V AC
4.1 Motor starter protector + contactor
Configuring SIRIUS Innovations
52 Configuration Manual, 04/2010, A8E56203880102-02
Standard three-phase motor
4-pole at 500 V AC
1)
Standard output P Motor current I
Setting range
Overload release
Motor starter protector
Motor starter
protector Motor
protection
Contactor
2)
kW A A Order No. Order No.
Size
11 17,6 17 ... 22 3RV2021-4CA10 3RT2026-1AP00 S0/S0
15 23 20 ... 25 3RV2021-4DA10 3RT2027-1AP00 S0/S0
18,5 28 23 ... 28 3RV2021-4NA10 3RT2027-1AP00 S0/S0
18,5 28 27 ... 32 3RV2021-4EA10 3RT2027-1AP00 S0/S0
Short-circuit breaking capacity I
q
= 36 kA
22
3)
33 30 ... 36 3RV2021-4PA10 3RT1035-1AP00 S0/S2
Order numbers for basic versions with screw terminals and spring-loaded terminals also possible.
1)
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
2)
Rated control supply voltage 230 V AC, 50 Hz, other possible.
3)
Discrete mounting only, without a link module.